Dry-Type Transformer

Dry-Type Transformer

Cast-resin dry-type transformers, 30–3,150 kVA — fireproof, low partial discharge, F/H insulation, AN/AF cooling. Compare dry vs oil-immersed and see when to choose dry.
Send Inquiry
Chat Now
Description

Why this transformer goes inside the building

 

dry type transformer

Dry-type transformers serve local lighting, high-rise buildings, airports, docks and machinery areas - precisely the places where an oil-filled unit is unwelcome. With no oil, there is no oil-fire or oil-leak risk, so a dry-type transformer can be installed directly at the load centre, shortening low-voltage runs and cutting losses. Cooling is by natural air (AN) or forced air (AF); AF raises the usable capacity at peak.

General specification

Parameter

Specification

Type

SC(B) cast-resin (epoxy) dry-type; SG dry-type

Rated capacity

30 – 3,150 kVA (10 kV class); larger on request

HV voltage

6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV (20 kV / 35 kV options)

LV voltage

0.4 kV (others on request)

Tap range

No-load: ±5 %, ±2 × 2.5 %; on-load: ±4 × 2.5 %

Vector group

Dyn11 / Yyn0

Insulation class

F (120 °C) / H (145 °C)

Cooling method

AN (natural air) / AF (forced air)

Partial discharge

≤ 10 pC (low-PD design)

Impedance voltage

≈ 4 – 6 %

Standards

IEC 60076, GB/T 10228, GB 6451

cast resin dry type transformer

 

Advantages & limitations of dry-type

 

01

Fireproof and pollution-free

No oil, no bund, no fire wall; insulating materials such as the winding glass fibre are self-extinguishing, and a short circuit will not sustain an arc.

02

No toxic emission under heat

The cast resin does not release toxic or harmful gases.

3

Installable at the load centre

Shorter LV runs, lower losses, no separate fire compartment.

04

Low / maintenance-free    No oil to test or replace.

 

 

05

Moisture-resistant

Suited to humid and severe environments.

06

High mechanical strength

The cast body has a concrete-like structure that withstands sudden short-circuit forces.

07

Low loss, low noise, low partial discharge, long life

 

08

Overload headroom

Forced-air (AF) cooling raises usable capacity at peak.

Limitations

Higher initial cost than an oil-immersed unit of the same rating.

Larger footprint / weight at higher ratings.

Lower maximum voltage (≈ 35 kV) and capacity than oil-immersed transformers.

Lower heat dissipation in still air - heavy duty needs AF cooling, and performance is more sensitive to ambient temperature.

Cast windings are not repairable on site - a damaged winding generally means replacement of the unit.

At very large ratings, oil-immersed is more economical.

 

dry type transformer advantages

Representative losses - SC(B) / SCB, 10 kV class

 

Capacity (kVA) No-load loss (W) Load loss @75 °C (W) F / H No-load current (%) Impedance (%)
100 290 1,410 / 1,520 1.7 4
250 515 2,480 / 2,660 1.3 4
400 705 3,590 / 3,850 1.1 4
630 965 5,290 / 5,660 0.9 4
1,000 1,275 7,310 / 7,830 0.9 6
1,600 1,765 10,550 / 11,300 0.9 6
2,500 2,195 15,450 / 16,540 0.7 6
3,150 3,110 18,490 / 19,800 0.7 6

 

Insulation level

Voltage grade (kV) Max operating voltage (kV) Power-frequency withstand (kV/min) Lightning impulse withstand (kV peak)
0.4 0.46 5 75
10 12 35 75
20 24 50 125
35 42 70 170

 

Dry-type vs oil-immersed - the differences that matter

Aspect Dry-type (cast resin) Oil-immersed
Insulating / cooling medium Solid cast resin + air Transformer oil
Fire risk No oil - fireproof, self-extinguishing Mineral oil is flammable (ester fluid reduces risk)
Where it can be installed Indoors, basements, upper floors, tunnels - at the load centre Outdoors or in a fire-separated room with oil bund
Fire protection required None (no bund, no fire wall) Fire wall, oil bund, extinguishing provision
Maintenance Low / maintenance-free - no oil tests Periodic oil testing and treatment
Leak / pollution risk None Oil-leak and disposal risk
Overload capability Good; AF forced cooling boosts capacity Good
Typical voltage / capacity Up to ≈ 35 kV; smaller ratings Up to 220 kV and above; large ratings
Footprint & weight Larger / heavier for a given rating More compact
Purchase cost Higher for the same rating Lower
Noise Low Low
Humid / harsh environment Solid insulation resists humidity Protected by the sealed oil system

 

Epoxy Resin Cast Coils for Dry Type Transformer
Epoxy Resin Cast Coils for Dry Type Transformer
Transformer Core Clamping Structure Assembly
Transformer Core Clamping Structure Assembly
Dry-Type Transformer Core & Coil Assembly
Dry-Type Transformer Core & Coil Assembly Detail
High Voltage Insulators & Busbar Connection Assembly
High Voltage Insulators & Busbar Connection Assembly

When should you choose a dry-type transformer?

Choose dry-type when any of these apply:

The transformer must sit indoors, at or near the load - high-rise and commercial buildings, hospitals, airports, tunnels and metro, basements.

Fire regulations restrict or prohibit oil-filled equipment in or near occupied spaces.

Oil leakage would be unacceptable - data centres, clean rooms, water treatment, public buildings.

Maintenance access is limited and a maintenance-free unit is preferred.

The environment is humid, corrosive or otherwise severe.

You need low loss, low noise and a long, maintenance-free life.

 

Choose oil-immersed instead when the priority is the highest voltage or capacity, an outdoor installation, lowest first cost, or the best heat dissipation at large ratings - see our oil-immersed power and distribution transformer pages.

 

Built for a long, quiet life

 

Vacuum and pressure casting. Resin mixing uses advanced agitation with a vacuum film-degassing step that removes bubbles. High- and low-voltage coils are cast under vacuum and pressure, giving both full encapsulation and turn-to-turn impregnation in a dense, cured body.

High mechanical strength. Filler in the resin minimises differential expansion and curing shrinkage, so internal stress is low and hardness is high. Pre-formed reinforcement inside the epoxy encapsulation produces a concrete-like structure that withstands sudden short-circuit forces without damage.

Low loss, low noise, maintenance-free. Losses and sound level are kept well below conventional figures, and there is no oil to test or replace.

 

SCB transformer

Insulation classes, cooling & environment

 

Cast-resin units are offered with F-class (120 °C) and H-class (145 °C) insulation. AN covers normal duty; AF forced-air cooling adds capacity at peak. Installation limits: altitude ≤ 2000 m and ambient −50 °C to +50 °C, with a supply waveform close to a sine wave.

Intelligent temperature control

Dedicated three-phase winding temperature monitors scan and display each phase, start and stop fans automatically, and provide alarm and trip set-points - protection is designed in, not bolted on.

Product families & applications

SC(B) series - cast-resin (epoxy) dry-type, 10 kV class, Dyn11 / Yyn0. SG series - dry-type units for general duty.

Applications: high-rise and commercial buildings · airports · tunnels and metro · docks and machinery areas · local lighting · any load-centre supply where oil is not acceptable.

 

To quote accurately, we need:

Rated capacity (kVA) and HV/LV voltage

Insulation class (F or H) and cooling method (AN / AF)

Connection group and tap range

Altitude, ambient temperature and humidity

Indoor/outdoor placement and any fire-regulation requirement

Applicable standard (IEC 60076 and/or GB series)

 

 