Products Description
Electrical Grade Insulation Crepe is a type of insulating paper, which is reprocessed from cable paper made of sulfate pulp. It has very good electrical properties in oil, showing a high average breakdown voltage and a small tangent value of the dielectric loss angle. Crepe paper is mainly used for wrapping the outgoing wires of transformers. Our company produces and provides electrical-grade insulation crepe paper, which complies with IEC 60554-3-5 standards and is widely used for power distribution and power transformer lead wire and coil insulation.
Product advantages:
Product Display




Typical Applications In Transformers:
Electrical Grade Insulation Crepe is suitable for manufacturing transformer electromagnetic wires or other electrical insulation equipment and is mainly used in the manufacture of commutation transformers.


Product performance parameters
Property |
Unit |
Stand ard |
||||
Thickness and tolerance |
mm |
0.35±0.05 |
0.46±0.05 |
0.65±0.1 |
0.8±0.1 |
Heat- resisting 0.55±0.88 |
Roll width |
mm |
550±2 |
550±2 |
550±2 |
1100±3 |
550±2 |
Base weight |
g/m² |
86-96 |
126-136 |
180-190 |
280-290 |
140-170 |
Density |
g/cm³ |
0.15-0.3 |
0.2-0.35 |
0.21-0.44 |
0.24-0.37 |
0.21-0.38 |
Tensile strength |
Kg/15mm |
MD≥2.0 |
MD≥4.0 |
MD≥6.0 |
MD≥6.0 |
MD≥5.0 |
Elongation |
% |
MD≥100 |
MD≥100 |
MD≥100 |
MD≥80 |
MD≥100 |
Breakdown voltage |
kV |
Ave.≥1.00 |
Ave.≥1.10 |
Ave.≥1.30 |
Ave.≥1.50 |
Ave.≥1.20 |
Min.≥0.70 |
Min.≥0.80 |
Min.≥1.00 |
Min.≥2.01 |
Min.≥0.90 |
||
Nitrogen content |
% |
-- |
-- |
-- |
-- |
1.3-3.0 |
Moisture Content |
% |
≤10 |
||||
Ash Content |
% |
≤0.7 |
||||
Protube 73n00s |
Nu mbers/inch |
≥20 |
We are a professional manufacturer of insulation materials, support ODM/OEM, please contact us to get free samples
packing
Electrical Grade Insulation Crepe packaged in wooden crates, wooden framed cases or other strong enough materials covered with moisture-proof materialoutside.Gross weight of each package not exceeds 3000kgs.




About us:
Principle
- High quality products, excellent service and a good reputation.
Service
- Effective communication within 24 hours
- New design and style collection updating for customer.
Quality Contral
- 5 quality control staff
- Providing relative solution
- Test the raw materials and give a report
- ISO,CE ,SGS approved.
Production process





Factory Display




FAQ
Q: I don't see my designed dimensions/ packaging/ delivery etc. Can you make a special order for us?
A: Sure. We're truly customized. You're free to tell us whatever you want.
Q: Do you deal with urgent orders?
A: Sure. Please contact ASAP for details.
Q: I bought from you once. Can I have a special offer this time?
A: Contact for details. We do value our customers; we can and will offer you good price.
transformer tips
Mechanical strength of paper insulation materials.
In addition to the fiber composition, density, permeability and uniformity of the paper, the most important factors in selecting paper insulation materials for oil-immersed transformers also include mechanical strength requirements, including tensile strength, punching strength, tear strength and toughness:
① Tensile strength: When the paper fiber is subjected to a tensile load, it is required to have the maximum stress that it can withstand without being broken.
② Punching strength: A measure of the ability of paper fibers to withstand pressure without being broken.
③ Tear strength: The force required to tear paper fibers is required to meet the corresponding standards.
④ Toughness: The strength of paper when folded or cardboard is bent can meet the corresponding requirements.