t Description
Transformer Electrical Insulating Paper DDP is made of imported pulp base paper, pure epoxy resin, and the most advanced foreign formula technology.
Product curing conditions:
First, keep it at 90℃±5℃ for 3 hours, then raise the temperature to 125℃±5℃ and keep it for 6 hours to achieve complete curing.
Storage:
Transformer Electrical Insulating Paper DDP should be stored in a dry and clean room with a temperature not higher than 25℃, and should not be near fire, heating or sunlight. The storage period is one year. If the storage period exceeds, it can still be used after passing the inspection.
| Diamond dotted paper (DDP) | ||||||||
|---|---|---|---|---|---|---|---|---|
| NO. | Project | Unit | 0.08 | 0.13 | 0.18 | 0.2 | 0.25 | |
| 1 | Thickness & tolerance | mm | 0.080±0.005 | 0.130±0.007 | 0.180±0.010 | 0.200±0.010 | 0.250±0.010 | |
| 2 | Density | g/㎡ | 0.85 - 1.1 | 0.85 - 1.1 | 0.85 - 1.1 | 0.85 - 1.1 | 0.85 - 1.1 | |
| 3 | Moisture content | % | 4.0 - 8.0 | 4.0 - 8.0 | 4.0 - 8.0 | 4.0 - 8.0 | 4.0 - 8.0 | |
| 4 | Water extract PH | - | 6.5 - 8.5 | 6.5 - 8.5 | 6.5 - 8.5 | 6.5 - 8.5 | 6.5 - 8.5 | |
| 5 | Ash content | % | ≤1.0 | ≤1.0 | ≤1.0 | ≤1.0 | ≤1.0 | |
| 6 | Adhesive thickness | μm | 6~12 | 6~12 | 6~12 | 6~12 | 6~12 | |
| 7 | Oil absorbency | % | ≥20 | ≥20 | ≥20 | ≥20 | ≥20 | |
| 8 | Contamination to transformer oil | No contamination | ||||||
| 9 | Bond strength | KPa |
Normal: ≥650 100℃±2℃: ≥400 |
Normal: ≥650 100℃±2℃: ≥400 |
Normal: ≥650 100℃±2℃: ≥400 |
Normal: ≥650 100℃±2℃: ≥400 |
Normal: ≥650 100℃±2℃: ≥400 |
|
| 10 | Tensile strength | N/10mm |
MD: ≥60 TD: ≥30 |
MD: ≥110; TD: ≥50 |
MD: ≥160; TD: ≥70 |
MD: ≥180; TD: ≥80 |
MD: ≥230; TD: ≥100 |
|
| 11 | Elongation | % | MD: ≥2.0; TD: ≥4.0 | MD: ≥2.0; TD: ≥4.0 | MD: ≥2.0; TD: ≥4.0 | MD: ≥2.0; TD: ≥4.0 | MD: ≥2.0; TD: ≥4.0 | |
| 12 | Tear strength | MN | MD: ≥450; TD: ≥500 | MD: ≥900; TD: ≥1000 | MD: ≥1350; TD: ≥1500 | MD: ≥1500; TD: ≥1700 | MD: ≥2000; TD: ≥2300 | |
| 13 | Breakdown voltage | KV | In air: ≥0.8; In oil: ≥4.00 | In air: ≥1.37; In oil: ≥7.00 | In air: ≥2.00; In oil: ≥9.00 | In air: ≥2.10; In oil: ≥9.80 | In air: ≥2.25; In oil: ≥11.5 | |
Product display




Application


Video